| No. | Requirement to be tested | TTA |
| 1 | Overtemperature limit | Proof of overtemperature limit by testing (type testing) |
| 2 | Insulation | Proof of insulation by testing |
| 3 | Short-circuit resistance | Proof of short-circuit resistance by testing (type testing) |
4 |
Effectiveness of the PE conductor circuit Proof of the perfect connection between bodies, switchgear assemblies and PE conductor circuits Short-circuit resistance of the PE conductor circuit |
Proof of the perfect connection between bodies of the switchgear assembly and PE conductor circuit (type testing) Proof of the short-circuit resistance of the PE conductor by testing (type testing) |
| 5 | Creepage distances and clearances | Proof of creepage distance and clearances (type testing) |
| 6 | Mechanical function | Proof of mechanical function (type testing) |
| 7 | IP protection category | Proof of IP protection category (type testing) |
| 8 | Wiring, electrical function | Viewing of switchgear assemblies including wiring and electrical function testing if necessary (unit testing) |
| 9 | Insulation | Insulation testing (unit testing) |
| 10 | Protective measures | Checking of protective measures and continuous PE conductor circuits (unit testing) |
| 11 | Insulation resistance | Proof of insulation resistance if test was not carried out |
| No. | Requirement to be tested | PTTA |
| 1 | Overtemperature limit | Proof of compliance with overtemperature limit by testing or extrapolation |
| 2 | Insulation | Proof of insulation by testing or proof of insulation resistance |
| 3 | Short-circuit resistance | Proof of short-circuit resistance by testing or extrapolation of similar type-tested assemblies |
4 |
Effectiveness of the PE conductor circuit Proof of the perfect connection between bodies, switchgear assemblies and PE conductor circuits Short-circuit resistance of the PE conductor circuit |
Proof of the perfect connection between bodies of the switchgear assembly and PE conductor circuit Proof of the short-circuit resistance of the PE conductor circuit by testing or respective design and arrangement of the PE conductor |
| 5 | Creepage distances and clearances | Proof of creepage distance and clearances |
| 6 | Mechanical function | Proof of mechanical function |
| 7 | IP protection category | Proof of IP protection category |
| 8 | Wiring, electrical function | Viewing of switchgear assemblies including wiring and electrical function testing if necessary |
| 9 | Insulation | Insulation test or proof of insulation resistance |
| 10 | Protective measures | Checking of protective measures |
| 11 | Insulation resistance | Proof of insulation resistance if test was not carried out |