Power System Module busbar The modular system enables a basic configuration using vertical support rails and a three-phase supply to be installed for each rack. The system also has a redundant power supply configuration as a second power supply has been provided for each of the rails. The vertical support rails ensure that the slots can be used over the full height of the enclosure and the redundant supply comes from the second separate supply. Socket modules can be snapped into the support rails. The contact hazard protection design of the busbar ensures that socket modules do not have to be fitted in all of the slots. Socket modules are available in different county versions, i.e. IEC IEC320 C13, earthing-pin, F/B, CH, USA & UK. A mixture of all of the modules can be fitted in the rails. 7 socket modules can be used with each 2m rail. A total of 42 sockets are available if IEC320 modules are fitted.
Installation via the plug & play system: The busbar can be installed in a flexRack(i) without having to use an adaptor or can be retrofitted to all Rittal TS / PS racks using a DK7856.011 mounting kit. The power is supplied via a 5-pin connection socket using tension-spring technology. A pre-configured 3 m connection cable fitted with an IEC309 AC plug is also available. All of the socket modules can be upgraded whilst working.
3-phase overvoltage protection: Overvoltage protection is available for every 3-phase supply. Overvoltage protection can also be fitted as an upgrade. Integrated visual function checks Overvoltage protection has been designed to meet Class D requirements (different use with local sockets).
Technical fittings: 3-phase configuration with a max. of 3 16A per power circuit Two separate power circuits per support rail Redundant power circuit 2 has a completely separate potential from power circuit 1 The connection direction of the socket module can be selected to determine if power circuit 1 or redundant power circuit 2 will be used. A socket module can be upgraded whilst working Every module can be selected with / without an integrated circuit breaker
Technical specifications: Three-phase voltage range 110V - 400V AC 50/60 Hz, neutral line is not needed
Max. current per supply: 3 x 16A
Temperature application range: +5°C - +45°C
Humidity range: 5% - 95% relative humidity, non-condensing Protection category IP20 Aluminium H-section version
W x H x D [mm]: 60 x 1908 x 60 |